您的当前位置:首页正文

★电容柜元器件配选表,变压器电容补偿配置表

2020-09-11 来源:个人技术集锦
电容柜元器件配选表/变压器电容补偿配置表电容容量断路器交流接触器BSMJ-0.45-5-3DZ47-63/3P/D32ACFC19-25/10 AC220VBSMJ-0.45-8-3DZ47-63/3P/D32ACFC19-25/10 AC220VBSMJ-0.45-10-3DZ47-63/3P/D40ACFC19-25/10 AC220VBSMJ-0.45-15-3DZ47-63/3P/D40ACFC19-32/10 AC220VBSMJ-0.45-18-3DZ47-63/3P/D40ACFC19-32/10 AC220VBSMJ-0.45-20-3DZ47-63/3P/D63ACFC19-43/10 AC220VBSMJ-0.45-25-3DZ47-63/3P/D63ACFC19-63/10 AC220VBSMJ-0.45-30-3DZ47-63/3P/D63ACFC19-63/10 AC220VBSMJ-0.45-40-3DZ47-100/3P/D100ACFC19-95/10 AC220V变压器容量30KVA及以下50KVA63,80KVA100KVA125KVA160KVA200KVA250KVA315KVA400KVA500KVA630KVA800KVA1000KVA1250KVA1600KVA2000KVA2500KVA电容补偿总容量5-8Kvar15Kvar20Kvar30Kvar40Kvar50Kvar60Kvar80Kvar100Kvar120Kvar150Kvar200Kvar240Kvar300Kvar400Kvar500Kvar600Kvar800Kvar共*路1*8Kvar1*15Kvar2*10Kvar3*10Kvar4*10Kvar3*15Kvar+1*5Kvar4*15Kvar4*20Kvar5*18Kvar+1*10Kvar6*20Kvar6*20Kvar+2*15Kvar6*30Kvar+2*10Kvar8*30Kvar10*30Kvar10*40Kvar10*25Kvar*210*30Kvar*210*40Kvar*2热继电器JR36B-20 6.8-10AJR36B-32 10-16AJR36B-32 14-22AJR36B-32 20-32AJR36B-32 20-32AJR36B-63 28-45AJR36B-63 25-45AJR36B-63 40-63AJR36B-160 53-85A适用柜宽100mm间隔100mm间隔200mm间隔300mm间隔600mm柜宽600mm柜宽600mm柜宽600mm柜宽800mm柜宽800mm柜宽1000mm柜宽1000mm柜宽1000mm柜宽1000mm柜宽*2层1000mm柜宽*2层1000mm柜宽*2层*2台1000mm柜宽*2层*2台1000mm柜宽*2层*2台一次导线BV 4mm2BV 4mm2BV 6mm2相关标准

GB 50227-2008 并联电容器装置设计规范

圆筒形的电容间距5CM就可以,椭圆或是方形的话要大于20CM一般为5-10CM

国家产品强制性认证(3C认证)中要求,补偿柜中电容器的安装间距不小于BV 6mm2BV 6mm2BV 10mm2BV 10mm2BV 10mm2BV 16mm2隔离开关(A)200A200A200A200A400A400A400A600A600A1000A1000A600A*2台1000A*2台1000A*2台换D型的电容保护等同于电动机保护

变压器多大,后面的电容柜的容量:百分之30补偿

ABB电容安装间距离墙/柜体间距CLMD13,332020CLMD43,53,63,835050

要大于20CM

补偿柜中电容器的安装间距不小于30mm,距地不小于20mm。

因篇幅问题不能全部显示,请点此查看更多更全内容